6.1.3.4 BACnet Configuration
Device Instance This is a 22-bit value (04,194,303). Each BACnet network device
must have a unique device instance. The default value is 2749.
UDP Port The default value of 0xBAC0 should usually not be changed.
BBMD IP Address Enter the address of the BBMD with which the BAS Remote will
perform Foreign Device Registration (FDR) if the BBMD is not
located on the same subnet as the BAS Remote.
BBMD Reg Time Enter the interval (in seconds) between successive foreign device
registrations.
Figure 18 Configuring BACnet in the Master Module