TD040300-0MF
11
3.4 Protocol Compliance
Protocol
Compliance
BACnet/IP
ASHRAE 135-2008 annex J.
Application specific controller device profile B-ASC.
Modbus TCP
Modbus Application Protocol Specification V1.1b Dec. 28, 2006, Modbus.org.
Modbus Messaging on TCP/IP Implementation Guide V1.0b October 24, 2006,
Modbus.org.
Modbus serial
Modbus over Serial Line Specification and Implementation Guide V1.02 December
20, 2006, Modbus.org.
3.5 Power Requirements
Item
Limits
Input power
Master module: 24 VAC/VDC ± 10%, 4763 Hz, 17 VA
Master PoE module: 48 VDC ± 10% 10 W
Expansion module: 24 VAC/VDC ± 10%, 4763 Hz, 17 VA
Loop supply
+24 VDC nom, 150 mA maximum
3.6 General Specifications
Item
Description
Protection
All inputs and outputs (except for relay outputs and communications ports) are
over-voltage protected up to 24 VAC and short-circuit protected.
Environmental
Operating temperature 0° to +60°C.
Storage temperature 40°C to +85°C.
Relative humidity 10 to 95%, non-condensing.
Weight
0.6 lbs. (0.27 kg).