Contemporary-control-systems BASrouter Installation Guide (Firmware 2.x) Instrukcja Użytkownika Strona 5

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 24
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 4
TD071200-0IK
5
2 Specifications
2.1 Electrical
INPUT DC AC
Voltage (±10%): 24 V 24 V
Power: 2 W 4 VA
Frequency: N/A 4763 Hz
2.2 Environmental
Operating temperature: 0°C to 60°C
Storage temperature: 40°C to +85°C
Relative humidity: 1095%, non-condensing
2.3 Mounting
2.4 Functional
Ethernet MS/TP
Physical Layer: 10BASE-T EIA-485
100BASE-TX
Cable length limit: 100 m 1200 m (for AWG 18)
MS/TP Baud rate (bps): 9600, 19200, 38400, 76800
MS/TP node limit: 254 devices total,
31 full-load devices per segment
MS/TP LED: flashing green = receive valid activity
Ethernet LED: green = 100 Mbps
yellow = 10 Mbps
flashing = activity
2.5 Regulatory Compliance
CE Mark; RoHS; CFR47, Part 15 Class A
2.6 Electromagnetic Compatibility
Each unit complies with Class A radiated and conducted emissions
as defined by EN55022 and CFR 47, Part 15. This equipment is
intended for use in non-residential areas.
Warning This is a Class A product as defined in EN55022. In a domestic
environment this product may cause radio interference in which case the
user may be required to take adequate measures.
TS-35 DIN-rail
(Class 2 Circuits Only)
Przeglądanie stron 4
1 2 3 4 5 6 7 8 9 10 ... 23 24

Komentarze do niniejszej Instrukcji

Brak uwag